# IDRAC8
|
|
|
|
## temperatureProbeReading
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.700.20.1.6 (temperatureProbeReading)
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.700.20.1.8 (temperatureProbeLocationName)
|
|
|
|
Here the temperatureProbeReading.1.1 is the inlet temp, temperatureProbeReading.1.2 is the exhaust temp, temperatureProbeReading.1.3 is the CPU1 temp and temperatureProbeReading.1.4 is CPU2 temp.
|
|
|
|
These are integers and are written like 250, so decimal needs to be moved to the left to get 25.0
|
|
|
|
## hostname
|
|
|
|
.1.3.6.1.2.1.1.5.0 (sysName)
|
|
|
|
Gets the hostname
|
|
|
|
|
|
## Power
|
|
.1.3.6.1.4.1.674.10892.5.4.600.12.1.16 (powerSupplyCurrentInputVoltage)
|
|
|
|
input voltage for PSU(s)
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.600.60.1.15 (powerUsageIdlePower)
|
|
|
|
Divide by 2 to get power usage
|
|
|
|
### To get per PSU power in watts
|
|
|
|
Multiply Amperage by Voltage:
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.600.30.1.6 (amperageProbeReading)
|
|
|
|
1.1 is PSU1 and 1.2 is PSU2
|
|
|
|
Amperage is in hundreds of miliamps. So if amperageProbeReading read 2, it means that PSUx is drawing 0.2 Amps
|
|
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.600.20.1.6 (voltageProbeReading)
|
|
|
|
1.31 is PSU1 and 1.32 is PSU2
|
|
|
|
Here the voltage i given without deicmal point (240000) so decimal point needs to be moved (240.000) or just convert to int (240)
|
|
|
|
|
|
|
|
## other
|
|
|
|
.1.3.6.1.4.1.674.10892.5.4.1100.30.1.23 (processorDeviceBrandName)
|
|
|
|
Get the CPU name(s)
|
|
|
|
.1.3.6.1.4.1.674.10892.5.2.5.0 (systemPowerUpTime)
|
|
|
|
Uptime in seconds |